Cooling · Water treatment

Data center water treatment: cooling tower and closed-loop programs, sized and quoted

A data center water treatment program controls scale, corrosion, fouling and microbes, including Legionella, in the open cooling tower or adiabatic water and in the closed loops behind it, among them the technology cooling system (TCS) that feeds liquid-cooled racks. In the open tower it also sets how much water you buy: makeup replaces evaporation, blowdown and drift, and the cycles of concentration your water chemistry allows decide the blowdown.1 Size your tower's water use with the calculator below, check what a proposal must include, then send one request and we'll try to match it with up to three independent treatment providers. We're a referral service; we don't treat water or test it.

Updated · How we research

What a data center water treatment program covers

A complete program covers every water or water-glycol loop in the cooling plant, not only the cooling tower. In a typical chilled-water data center, heat moves from the IT equipment to the chilled water, from the chiller to the condenser water, and from the condenser water to the cooling tower, which rejects it by evaporation.4 In a direct liquid cooled design, a closed loop carries heat from the racks to a coolant distribution unit (CDU), where it passes to the condenser water and the tower.4 The OCP guideline for these loops calls the CDU-to-cold-plate loop the technology cooling system (TCS) and the facility-side loop the facility water system (FWS).15

Where water treatment applies in a data center cooling plant An open cooling tower at the top receives makeup water and loses water to evaporation, drift and blowdown. Condenser water runs from the tower to a chiller or heat exchanger; this open loop needs scale, corrosion, fouling and microbiological control plus a Legionella water management program. Below it a closed facility water loop runs to a coolant distribution unit and needs corrosion inhibitor, filtration and bacteria checks. Below that a closed technology cooling system loop runs to cold plates and needs PG25 or treated water, fine filtration and lab analysis. Evaporation Drift Makeup Blowdown to sewer Open cooling tower or adiabatic unit Chiller or HX CDU Cold plates Open loop condenser Scale, corrosion, fouling, biology, Legionella plan Closed loop facility water Inhibitor, filtration, bacteria checks Closed loop TCS PG25 or treated water, filters, lab analysis Not every site has every loop.
Three loops, three treatment jobs. The open tower loses water and concentrates minerals; the closed loops keep their fluid and must keep it clean and inhibited. Some sites skip the chiller (water-side economizer, dry coolers) or the tower (air-cooled heat rejection). Our diagram, based on FEMP's data center schematics and the loop names in the OCP TCS guideline.415

Each loop needs a different kind of treatment. The table sets out what a program has to do in each.

Data center water treatment scope by system type. Sources as cited in each row; "what can go wrong" summarizes the cited guidance.
SystemOpen or closedWhat can go wrongMain program elements
Open evaporative cooling tower (condenser water)Open: evaporates and concentrates mineralsScale, corrosion, fouling from airborne dirt, biological growth, Legionella in drift25Automated chemical feed and blowdown, conductivity control, disinfectant residual, side-stream filtration where dirt load justifies it, annual offline cleaning, a written water management program15
Closed-circuit tower or evaporative condenserSpray water is open; the coil loop is closedSame spray-side risks as an open tower; CDC says Legionella can grow in both open and closed-circuit towers5CDC says open and closed-circuit towers need the same basic operation and maintenance protocols; the fluid inside the coil is a closed loop of its own5
Adiabatic or direct evaporative unitsOpen water on pads, media or spraysScale and fouling on media, microbiological growth16Scale inhibitor, antimicrobial treatment, media-compatible chemistry, Legionella sampling plan16
Chilled water or facility water loopClosedCorrosion, contamination and debris left by incomplete cleaning or flushing19Pre-operational cleaning, flushing and passivation, corrosion inhibitor, monitoring1819
TCS loop to cold platesClosed, small passagesParticles blocking microchannels, glycol or inhibitor drift, contamination at service events15Inhibited PG25 or treated water, specified dilution water, filtration, flushing at commissioning, lab analysis on a schedule15

For the cooling hardware itself, see our guides to direct-to-chip and other liquid cooling options and the cooling equipment makers and integrators.

Adiabatic and direct evaporative systems

Adiabatic coolers and direct evaporative units use far less water than a tower in most hours, but the water they do use still concentrates and still needs a plan. Microsoft says that in its direct evaporative systems, water flows in when the temperature exceeds 85°F and cycles through the system two to five times before the unevaporated remainder is discharged.10 ASHRAE Guideline 12 reviews air coolers, misters and humidifiers alongside cooling towers as Legionella risk areas.6 ChemTreat's adiabatic services include media-compatibility testing, scale inhibitors, antimicrobial treatment and Legionella sampling, which is a useful outline of what to ask any vendor for.16

The four things treatment controls: scale, corrosion, fouling and microbes

Every cooling water program is built around four control goals, and a weakness in one undermines the others. Veolia's handbook notes that corrosion inhibitors and deposit control agents cannot work properly under biological deposits.2

The four control goals in open recirculating cooling water. Sources: Veolia Water Handbook chapter 31; DOE FEMP BMP #10; CDC cooling tower module.
GoalWhy it happensTypical controlsHow it's checked
ScaleEvaporation leaves minerals behind; calcium carbonate, one of the least soluble salts, is a common scale former, and many salts become less soluble at higher temperature or pH2Blowdown control, acid feed, softening, scale inhibitors21Langelier and Ryznar indices, deposits on coupons or test exchangers2
CorrosionHigher dissolved solids raise conductivity; Veolia says inhibition gets harder and more expensive near and above 10,000 µmho2Corrosion inhibitor programs, plus a specific copper inhibitor where copper alloys are present2Corrosion coupons, corrosion rate meters, iron and copper in the water2
FoulingSilt, mud, iron and airborne debris settle in low-flow areas such as the basin and exchangers2Side-stream filtration, dispersants, basin cleaning12Equipment inspection; suspended solids in makeup versus blowdown2
MicrobiologicalWarm water, long retention and nutrients from the air favor growth2Oxidizing or non-oxidizing biocides, automated feed, cleaning, tower deck covers51Disinfectant residual, growth on real or test surfaces, Legionella culture tests528

Legionella and the water management program (ASHRAE 188, CDC)

Cooling towers need a written Legionella water management program, because tower drift can carry the bacteria over long distances. CDC says aerosolized water from a contaminated tower can spread Legionella over miles.5 ASHRAE Standard 188 sets minimum requirements for legionellosis risk management, including a building survey, the principles of a water management program and design requirements; ASHRAE Guideline 12 gives guidance for complying with it, including a review of cooling towers and condensers.6 The edition ASHRAE's purchase link points to is 188-2021.6

CDC's seven steps for building the program are:7

  1. Establish a team. In-house staff, outside experts or both, with Legionella experience.
  2. Describe the water systems. Flow diagrams and a written description, including where the cooling towers are.
  3. Identify where Legionella could grow and spread. Warm water, low flow, dead legs.
  4. Set control measures, limits and points, and how to monitor them. For example, a detectable disinfectant level, and a pH measurement to confirm the disinfectant will work.
  5. Set corrective actions for when a control limit is missed.
  6. Verify and validate. Confirm the plan is followed and that it works; Legionella testing is one validation option.
  7. Document and communicate everything, and retrain when the plan changes.

For towers specifically, CDC recommends high-efficiency drift eliminators, siting towers at least 25 feet from building air intakes, operating, where possible, below the 77 to 113°F (25 to 45°C) range that favors Legionella growth, flushing low-flow pipe runs and dead legs at least weekly, and an offline cleaning and disinfection at least once a year.5 It also recommends automating anti-corrosion, anti-scale and disinfectant feed and monitoring, and automated blowdown.5

When testing is used, CDC treats a cooling tower result under 10 CFU/mL as well controlled; 10 CFU/mL or more means conditions may allow growth, a 10- to 100-fold increase means poorly controlled growth and more than 100-fold means uncontrolled growth.8 CDC adds that there's no known safe level of Legionella and that any detection should trigger a response.8 Ask whether the lab is accredited for Legionella methods, for example to ISO/IEC 17025; culture results typically take 7 to 14 days.8

How much water a cooling tower uses: evaporation, blowdown and makeup

A cooling tower's makeup water is its evaporation plus its blowdown (plus drift and any leaks), and only the blowdown is really up for negotiation. DOE FEMP says carefully monitoring and controlling blowdown is the most significant opportunity to save water in cooling tower operations.1

  • Evaporation carries the heat away. About 1,000 Btu leaves the water for every pound evaporated, which works out to roughly 1% of the recirculating flow for every 10°F of range.2 EPA puts it at about 1.8 gallons evaporated per ton-hour of cooling, regardless of tower efficiency.3
  • Blowdown removes concentrated water so minerals don't scale or corrode the system. For the water balance, Veolia counts all non-evaporative losses (drift, windage, leaks and intentional bleed) as blowdown, and blowdown = evaporation ÷ (cycles − 1).2
  • Drift is small with modern eliminators. EPA says eliminators can cut drift to less than 0.005% of the flow through the tower; SPX says drift is typically 0.01% or less and does not change total water use, because whatever leaves as drift no longer has to leave as blowdown.39

The range (hot water temperature minus cold water temperature) is usually 10 to 25°F, and towers are typically designed for a 7 to 15°F approach to the wet bulb.2 For a given heat load, the range changes the recirculation rate but not the evaporation: a wider range means less flow over the tower, with the same heat removed by the same amount of evaporation.

Cooling tower water-use calculator

Calculator

Evaporation

30 gpm

Blowdown

10 gpm

Makeup

40 gpm

Recirculation

3,000 gpm

Makeup per kWh of heat rejected

2.07 L/kWh

How it works: heat rejected (Btu/h) is 15,000 per refrigeration ton (12,000 of cooling plus compressor heat, consistent with EPA's 1.8 gallons per ton-hour) or 3,412 per kW. Recirculation (gpm) = Btu/h ÷ (500 × range). Evaporation (gpm) = recirculation × range × F ÷ 1,000, Veolia's handbook equation, where F = 1 assumes all heat leaves by evaporation (real towers run about 0.75 to 1.0). Blowdown = evaporation ÷ (cycles − 1) and counts drift, leaks and intentional bleed together. Makeup = evaporation + blowdown. Design-day planning estimate only: annual use is lower when load and wet bulb drop, and it is not a substitute for metered data or your treatment vendor's water balance.

Worked example (the calculator's defaults). 1,000 refrigeration tons at the chillers rejects about 15,000,000 Btu/h at the tower. At a 10°F range that's 3,000 gpm of recirculating water. Evaporation is 3,000 × 10 × 1.0 ÷ 1,000 = 30 gpm, or 1,800 gallons an hour, which matches EPA's 1.8 gallons per ton-hour.23 At 4 cycles, blowdown is 30 ÷ 3 = 10 gpm and makeup is 40 gpm: about 57,600 gallons a day, or 21 million gallons a year at constant full load.

The 15,000 Btu/h per ton allows for compressor heat on top of the 12,000 Btu/h of cooling. FEMP says chiller compressor heat can be up to 20% of the total heat a data center tower rejects, which is exactly that split (3,000 of 15,000).4 If your plant runs on a water-side economizer, or your liquid cooling rejects straight to the tower without a chiller, enter the heat in kW instead; FEMP notes that economizing removes the compressor's share of the heat.4

Cooling tower water use per 1 MW (1,000 kW) of heat rejected, by cycles of concentration. Our calculation with the equations above: range-independent, F = 1.0, constant full load, 8,760 hours a year. Gallons are US gallons.
CyclesEvaporation (gal/day)Blowdown (gal/day)Makeup (gal/day)Makeup (million gal/yr)Makeup per kWh of heat (L)
29,8279,82719,6547.173.10
39,8274,91314,7405.382.32
49,8273,27613,1034.782.07
59,8272,45712,2844.481.94
69,8271,96511,7924.301.86
109,8271,09210,9193.991.72

Real annual use is lower than the table when load or wet bulb falls: SPX warns that using peak load or the design wet bulb for a year-round estimate overstates consumption, and Veolia puts the real evaporation factor between about 0.75 and 1.0.92

The table shows where the savings flatten. Going from 2 to 4 cycles cuts makeup by a third; going from 6 to 10 saves about 7% more. FEMP's figure for moving from 3 to 6 cycles is a 20% cut in makeup, which matches the equations.1

Cycles of concentration: how high you can run

Cycles of concentration is the ratio of dissolved solids in the blowdown to those in the makeup, and it's also roughly the ratio of makeup volume to blowdown volume.1 At 3 cycles, the blowdown carries three times the solids of the makeup.2 FEMP says many systems run at two to four cycles, while six or more may be possible; the ceiling depends on your makeup water and the treatment program.1

Cycles ceiling estimator

Screening tool

Enter your makeup water analysis. The limits are pre-filled with the maximum concentrations EPA WaterSense reprints from the U.S. Green Building Council; replace them with your treatment vendor's control limits.3

Estimated cycles ceiling

5 cycles

Limiting parameter

Conductivity

How it works: each parameter allows cycles = limit ÷ makeup value, and the lowest one sets the ceiling. With the defaults, conductivity limits the tower to 5.0 cycles (2,000 ÷ 400). Treatment changes the answer: scale inhibitors, acid feed or softening can let a program run above plain solubility limits, and Veolia's handbook shows one makeup water limited to 2 cycles untreated but treatable at 10.2 Screening only; your vendor sets the real limits from a full analysis.

Physical losses also cap cycles. Veolia notes that drift of up to 0.2% of recirculation in older towers can limit cycles to 5 to 10, while newer towers with efficient eliminators and no extra losses may be mechanically capable of 50 to 100 cycles or more; chemistry, not the tower, then becomes the limit.2

Ways to raise cycles safely

  • Conductivity-controlled blowdown. A controller measures conductivity and blows down only when the set point is exceeded; FEMP recommends working out the safe maximum with your treatment specialist.1
  • Acid feed. Converts part of the alkalinity into more soluble forms so the system can run at higher cycles. It needs trained handling and a timer or continuous pH monitoring, because acid overdoses can severely damage the system.1
  • Softening. Makeup or side-stream softening helps when hardness is the limiting factor.1
  • Side-stream filtration. Removes silt and suspended solids from part of the flow; useful in dusty locations.1 FEMP lists centrifugal separators, automatic screen filters, disc filters and sand filters as common types.4
  • Treating the makeup. AWS says some of its regions use on-site treatment to remove scale-forming minerals so the water can be cycled more times.13

Check that the cycles are real

Put flow meters on the makeup and blowdown lines and compare two ratios: makeup flow ÷ blowdown flow, and blowdown conductivity ÷ makeup conductivity. FEMP says they should both match the target; if not, look for leaks or unauthorized draw-off.1 EPA's rule of thumb is that if the flow-based cycles exceed the conductivity-based cycles by more than 10%, the tower may be losing water to a leak, overflow or excessive drift.3 Veolia adds that conductivity-based cycles can read slightly high because chlorine, acid and treatment chemicals add conductivity.2

WUE: how the treatment program shows up in the metric

Water usage effectiveness (WUE) is The Green Grid's site water metric: annual site water use in liters divided by annual IT equipment energy in kWh, reported in L/kWh.11 The water counted includes humidification and the water consumed for cooling, including cooling tower evaporation, blowdown and drift.11 So every gallon of blowdown a better program avoids comes straight off the WUE numerator. The Green Grid lists optimizing tower operations to increase cycles of concentration among the ways to improve WUE.11

The calculator's "makeup per kWh of heat rejected" figure is not WUE. WUE divides by IT energy only, while the tower also rejects chiller compressor heat, pump heat and other loads, so a site's tower contribution to WUE will be somewhat higher than the per-kWh-of-heat figure. The Green Grid also defines WUEsource, which adds the water used to generate the site's electricity; its suggested U.S. average energy water intensity factor is 1.8 L/kWh.11 For a national laboratory benchmark, FEMP reports that the NLR data center reached a PUE of 1.06 and a WUE of 0.7 with direct liquid cooling and a hybrid dry and evaporative system.4

Alternate water sources and local restrictions

Reclaimed water, recovered condensate and rainwater can replace potable makeup, but each brings its own chemistry, and the treatment program has to be designed for it. CDC recommends potable makeup or making sure reclaimed or condensate sources are appropriately managed.5

  • Reclaimed (recycled) municipal water. FEMP lists high-quality municipal wastewater effluent or recycled water among usable makeup sources where available.1 In Northern Virginia, Loudoun Water began building its reclaimed water system in 2010 to supply irrigation and industrial cooling water to data centers; it now has 20 miles of pipeline and delivered more than 750 million gallons in 2025. New connections are at the utility's discretion and can be limited by supply and hydraulics.12 AWS says it was the first data center operator Loudoun Water approved to use reclaimed water with direct evaporative cooling.13
  • Air handler condensate. FEMP calls it a particularly good fit, because it's low in minerals and is produced in the largest volumes when tower loads are highest.1
  • Rainwater. EPA lists collected rainwater and air conditioner condensate as makeup options.3 Microsoft says some of its data centers and facilities capture and reuse rainwater as part of broader water-efficiency efforts.10
  • Blowdown recovery by reverse osmosis. FEMP describes RO on tower blowdown as an option in drought-affected regions, returning permeate as makeup, but notes it raises energy use and PUE and adds operations and maintenance work.4
  • Sewer credits. Ask your utility whether it credits evaporation, calculated as metered makeup minus metered blowdown.1

Local water rules can also shape the program. In Tucson, Arizona, for example, the Large Quantity Water Users Ordinance, as the city's May 2026 data center fact sheet describes it, requires any project projected to use 10,000 CCF (about 7.48 million gallons) or more a month to submit a Sustainable Water Service Application and a Water Conservation Plan for Mayor and Council approval; a draft zoning amendment described in May 2026 would also prohibit potable water for cooling at data centers below that threshold.14 The fact sheet scheduled the Mayor and Council hearing for July or August 2026; we haven't confirmed the outcome. Check your own utility and municipality before fixing the makeup source and target cycles.

Closed loops and liquid cooling: TCS water quality

Closed loops don't evaporate water, so their treatment job is to keep the fluid clean, inhibited and stable for years. The OCP guideline on propylene glycol fluids, revised in September 2026, covers the TCS between the CDU and cold plate-cooled IT equipment, and explicitly leaves the facility water system out of scope.15 For how the TCS, FWS and CDU fit together in the cooling design, see liquid cooling loop architecture. The OCP guideline's main recommendations for PG25 loops:

  • Fluid. For PG25, the glycol content should test at 24 to 29% by volume, which corresponds to a freeze point of 9 to 15°F (−13 to −9°C).15
  • Filtration. The fluid should be filtered at 50 microns or finer, with 25 microns or finer preferred, before it ships. On site, sidestream filtration (typically 5 to 15% of the flow) is strongly recommended for systems over 250 gallons, and most CDUs also carry 25 or 50 µm inline filters. Size filtration for the smallest passages in the cold plates.15
  • Testing. Every TCS loop should be analyzed by a qualified lab at least once a year, covering glycol concentration, pH, reserve alkalinity, appearance, inhibitor levels, chloride, sulfate, hardness, degradation acids and dissolved metals.15
OCP suggested lab sampling for PG25 TCS loops, by risk level. Source: OCP Guidelines for Using Propylene Glycol-Based Heat Transfer Fluids in Liquid Cooled Racks, Rev. 2.0, Table 13 (September 2026). "Twice a year" is OCP's "bi-annual."
Risk levelSituationLab analysisOn-site testing
LowInline pH and refractive index monitoring; wetted materials acceptable; team familiar with the fluidAt commissioning, then annuallyNot required
MediumNo inline monitoring; materials acceptable; team not familiar with the fluidAt commissioning, then twice a year for 1.5 years; annual after that if stableTwice a year
HighNo inline monitoring; materials only mostly acceptable; team not familiar with the fluidAt commissioning, then quarterly for 1.5 years; twice a year after that if stableNot required

Make-up and dilution water matters too. OCP's dilution water specification calls for chloride and sulfate under 10 ppm each, total hardness under 15 ppm as CaCO₃, iron under 2 ppm, bacteria under 100 CFU/mL and conductivity under 25 µS/cm at 20°C, and it warns that softened water may not remove enough chloride and sulfate.15 That is why a treatment proposal for a liquid cooling build should name the water used for flushing, filling and top-ups, not only the inhibitor. Flushing and filling are usually part of commissioning; see our guide to data center commissioning and integrated systems testing.

Not every operator uses PG25. Microsoft says some of its data centers use a propylene glycol solution in closed loops, and ChemTreat lists both PG25 and PG50 fluids and aqueous coolants for direct-to-chip systems.1016 OCP notes that treated-water and dielectric fluids are handled in separate workstreams.15 Whatever the fluid, follow the cold plate and CDU makers' fluid requirements, and get them in writing before choosing a program.

Monitoring and service frequency

Most of the monitoring that matters runs continuously on controllers; people and labs then check the trend at set intervals. We found no standard that fixes how often a treatment vendor must visit, so agree the visit schedule and report contents in the contract. These are the published frequencies we could verify:

Published monitoring and maintenance frequencies for data center cooling water. Sources as cited in each row.
TaskFrequencySource
Conductivity and blowdown controlContinuous, by controllerDOE FEMP1
Read conductivity and flow meters; log makeup, blowdown and cyclesRegularly, to spot trendsDOE FEMP1
Oxidizing disinfectant residual (chlorine, bromine)Measurable throughout each dayCDC5
Flush low-flow pipe runs and dead legsAt least weeklyCDC5
Circulate water in a wet standby tower (down under 5 days)3 times a weekCDC5
Offline cleaning and disinfection of the towerAt least annuallyCDC5
Re-test after Legionella remediationAt least 48 hours after return to normal operationCDC8
TCS (PG25) lab analysisAt least annually per loop; more often by risk (see table above)OCP15

Monitoring of corrosion (coupons or corrosion rate meters), deposits and biological growth should also be on a stated schedule; Veolia's handbook notes that bulk water bacteria counts can mislead, and that monitoring growth on real or simulated surfaces gives a better picture.2 Tower inspection, basin and fill cleaning and the annual offline disinfection usually sit in the mechanical maintenance plan too; see how towers, chillers and CDUs fit a data center maintenance program.

What a water treatment proposal should include

Ask every bidder to price the same scope and to commit to measurable results, not only to a chemical list. FEMP's advice is to tell vendors water efficiency is a priority, ask them to estimate chemical quantities and costs, blowdown volumes and expected cycles, and compare them on cost to treat 1,000 gallons of makeup and on the highest cycles they recommend.1 FEMP also warns that some vendors may be reluctant to improve water efficiency, because it means selling fewer chemicals.1

A proposal you can compare should state:

  • Systems covered. Each tower, adiabatic unit, chilled water or facility water loop and TCS loop, with volumes.
  • Water balance. Target cycles, expected makeup and blowdown (show them the calculator figures above and ask them to correct the assumptions), and cost per 1,000 gallons of makeup.1
  • Control limits. Conductivity set point, pH range, inhibitor and biocide residuals, and the corrective action when each is missed.
  • Legionella role. Who writes and maintains the water management program, who sits on the team, how validation is done and which accredited lab runs any tests.78
  • Equipment and automation. Controllers, feed pumps, remote monitoring and alarms, and who owns them if the contract ends.
  • Service and reporting. Visit frequency, what is tested on site, the report format and how quickly results reach your team.1
  • Closed loops and TCS. Fluid type, dilution water specification, filtration, sampling plan and lab parameters (use the OCP list above).15
  • New builds. Pre-operational cleaning, flushing and passivation, fill-water quality checks and sign-off before handover.1916
  • Annual tower cleaning and disinfection. Included or priced separately.5
  • Discharge. Confirmation the blowdown chemistry meets your sewer permit; Veolia notes zinc and phosphate effluent limits are in place in many states.2
  • Chemical safety and delivery. Storage, containment, delivery method and safety data sheets.

What drives the price

We haven't found credible published pricing for data center water treatment contracts, so this page gives no dollar figures. Price turns on the number and size of systems, the makeup water chemistry, the target cycles, the level of automation and remote monitoring, visit frequency, lab testing and whether cleaning, filtration or reuse equipment is included. Comparing bids on FEMP's cost-per-1,000-gallons basis keeps the chemical price tied to the water it treats.1

Who provides data center water treatment

Data center water treatment is usually bought from a water treatment company that supplies the chemistry, the feed and control equipment and the field service, sometimes alongside separate filtration, reuse or testing specialists. The main provider types:

National treatment companies

Chemistry, automation, labs and local field service under one contract. The companies below publish data center or cooling water programs on their own sites.

Regional and independent treatment firms

Local service companies that supply and service treatment programs. Ask how they cover TCS loops and who runs their lab work.

Filtration, softening and reuse equipment makers

Side-stream filters, softeners and blowdown recovery systems, bought directly or through the treatment company.

Legionella consultants and labs

Water management program development, validation sampling and accredited testing. CDC suggests checking lab accreditation, for example to ISO/IEC 17025.8

National treatment companies that publish data center or cooling water programs, alphabetically. This list is editorial and unpaid. It isn't a ranking or a recommendation, and we have no agreements with any company named here. Descriptions come from each company's own site, checked November 27, 2026.

ChemTreat

Programs for cooling towers, closed loops, adiabatic systems and direct-to-chip cooling, including PG25 and PG50 fluids, pre-operational cleaning for facility and technology cooling systems, and inline monitoring and automated feed. Its page says it is part of Dow's Coolant Care Network.16

Ecolab (Nalco Water)

Data center cooling water programs for corrosion, scale and microbiological control, cooling tower cleaning and disinfection, Legionella water safety programs, treatment for process-critical closed loops and a white rust inhibitor, plus its 3D TRASAR cooling water technology.17

Kurita America

Cooling water treatment for open evaporative towers, evaporative condensers and closed loops, including pre-operational cleaning and passivation, white rust control, IoT monitoring and control, side-stream filtration and packaged blowdown recovery. The page we checked covers industrial, commercial and institutional systems and doesn't name data centers.18

Solenis

Data center water management covering design input, pre-commissioning cleaning, flushing and passivation, steady-state treatment and monitoring, Legionella risk management, liquid cooling support and water reuse. Its site says NCH is now part of Solenis.19

Veolia Water Technologies & Solutions

Data center services that, by Veolia's account, start with identifying a water source and add water treatment and reclamation equipment plus water chemistry programs; it says it also helps operators adopt closed-loop systems and alternative water sources such as treated municipal wastewater.20 Veolia also publishes the water treatment handbook cited on this page.2

For cooling equipment makers and integrators, see the directory of data center cooling companies.

Limits of this guide

The calculator uses standard engineering approximations (about 1,000 Btu per pound evaporated, F up to 1.0) at a constant load. It doesn't model wet bulb, part load, free cooling hours or drift separately, so annual figures are upper-bound planning numbers, not a substitute for metered data or a vendor's water balance. The cycles estimator uses U.S. Green Building Council limits as reprinted by EPA; a treatment program can change those limits. We describe ASHRAE Standard 188 and Guideline 12 from ASHRAE's and CDC's own summaries and didn't review the full text. The closed-loop guidance covers PG25 TCS loops per OCP's September 2026 guideline; treated-water and dielectric TCS fluids follow other documents. Rules for water use, discharge and Legionella vary by state and city. Nothing here is engineering advice.

What to send for an accurate quote

A treatment company can scope the work quickly if you send the systems, the load, the water and the problems:

  • Each system to cover: cooling towers (open or closed-circuit), adiabatic or evaporative units, chilled water or facility water loops, TCS loops, with tonnage or kW and loop volumes if known.
  • Design heat load, range and recirculation flow, or the calculator figures above.
  • Makeup source (potable, reclaimed, well, condensate) and a recent makeup water analysis.
  • Current cycles, conductivity set point and any metered makeup and blowdown data.
  • Known problems: scale, corrosion, fouled exchangers or cold plates, positive Legionella tests.
  • Whether you have a written water management program, and who owns it.
  • For new builds or liquid cooling retrofits: the commissioning schedule, flushing and fill plan, and the CDU and cold plate makers' fluid requirements.
  • Water goals or limits: WUE target, utility or municipal restrictions, discharge permit limits.

Put the essentials in the form and request quotes; providers may ask for the water analysis and drawings when they contact you.

Get water treatment quotes through Data Center Service Providers

Send one request with your systems, location and goals. A person reviews it and looks for up to three independent water treatment providers that serve your site and handle the systems you listed. If we can't find a match, we'll tell you. Providers contact you directly, and you decide whether to hire anyone. It's free for buyers. Providers may pay us a referral fee (see the referral disclosure); today we have no agreements with any provider. We're a directory and referral service, not a water treatment company, and we don't test water or supervise programs. Here's how requests are handled.

Request water treatment quotes

Sources

  1. Best Management Practice #10: Cooling Tower Management, U.S. Department of Energy, Federal Energy Management Program (FEMP), Last updated May 26, 2026. Water balance, cycles of concentration, typical cycles, controller and meter practice, acid feed, vendor selection, retrofit options and alternate makeup sources. Checked 2026-11-27.
  2. Water Handbook, Chapter 31: Open Recirculating Cooling Systems, Veolia Water Technologies & Solutions. Treatment vendor engineering handbook. Source of the evaporation equation (E = RR × ΔT × F ÷ 1,000), the evaporation factor range, the blowdown equation and typical approach, range and drift values. The live site timed out on November 26 and again on November 27, 2026; verified against a copy of this URL captured November 20, 2026. Checked 2026-11-27.
  3. Water Efficiency Management Guide: Mechanical Systems, U.S. EPA WaterSense. About 1.8 gallons evaporated per ton-hour; drift ranges; cycles equations; maximum concentrations table (from the U.S. Green Building Council); alternate makeup sources. Checked 2026-11-27.
  4. Cooling Water Efficiency Opportunities for Federal Data Centers, U.S. Department of Energy, FEMP, Last updated November 16, 2026. WUE equation, compressor share of tower heat rejection, side-stream filtration, RO on blowdown, direct liquid cooling. Checked 2026-11-27.
  5. Controlling Legionella in Cooling Towers, Centers for Disease Control and Prevention (CDC), Reviewed January 3, 2025. Checked 2026-11-27.
  6. Guidance for Water System Risk Management (Standard 188, Guideline 12, Standard 514), ASHRAE. Scope descriptions. The purchase links on this page point to Standard 188-2021; CDC links Guideline 12-2023. Checked 2026-11-27.
  7. Steps to Develop a Water Management Program, CDC, Reviewed March 15, 2024. Checked 2026-11-27.
  8. Routine Testing for Legionella, CDC, Updated January 3, 2025. Checked 2026-11-27.
  9. Evaporation and Water Usage (AE-AS-24-1), SPX Cooling Technologies. Cooling tower manufacturer application note. Checked 2026-11-27.
  10. Understanding water use at Microsoft datacenters, Microsoft Local, Modified October 15, 2026. Checked 2026-11-27.
  11. WP#35: Water Usage Effectiveness (WUE): A Green Grid Data Center Sustainability Metric, The Green Grid, 2011. Checked 2026-11-27.
  12. Reclaimed Water Program, Loudoun Water (Virginia). Checked 2026-11-27.
  13. Reducing water usage in AWS data centers, Amazon, August 11, 2020. Checked 2026-11-27.
  14. Regulations for Large-Scale Data Centers: Fact Sheet, City of Tucson, Arizona, Timeline as of May 28, 2026. Describes the Large Quantity Water Users Ordinance and a draft zoning code amendment. Checked 2026-11-27.
  15. Guidelines for Using Propylene Glycol-Based Heat Transfer Fluids in Liquid Cooled Racks, Revision 2.0, Open Compute Project (OCP), September 15, 2026. Sections 7 (filtration), 11.2 (sampling frequency, Table 13) and Appendix 1 (dilution water). Checked 2026-11-27.
  16. Water Treatment for Data Centers, ChemTreat, Modified May 18, 2026. Checked 2026-11-27.
  17. Data Center Cooling System Management, Ecolab (Nalco Water), Published August 11, 2026. Checked 2026-11-27.
  18. Cooling Water Treatment Solutions, Kurita America. General cooling water page; it does not mention data centers by name. Checked 2026-11-27.
  19. Data Centers: Mission-Critical Water Management for High-Performance Data Center Cooling, Solenis. Checked 2026-11-27.
  20. How Data Centers Can Solve Their Water Consumption Challenge, Veolia Water Technologies (company blog), July 23, 2025. Veolia's data center landing page (watertechnologies.com/industries/data-centers) timed out on November 26 and 27, 2026, so the directory description uses this Veolia-published article instead. Checked 2026-11-27.