How this directory was built
We started from the US Google results for “data center cooling companies” and “data center liquid cooling companies” on November 26, 2026, and the manufacturers those pages name most often. We kept a company only if its own website, or its parent's, describes data center cooling products, and we read those pages that day and again on November 27, 2026. Each description quotes or paraphrases them, and every ownership change comes from the buyer's or the company's own announcement. A “Yes” in the capability table means we found that product type on the company's site; a dash means we didn't find it there, not that the company doesn't offer it. Product claims are the companies' own and we haven't tested any equipment. Companies we found but didn't fully check this round, including Alfa Laval, Asperitas, DCX and Delta Electronics, are left off for now.
No company paid to be listed, and Data Center Service Providers has no referral, advertising or partnership agreement with any company on this page. See our referral disclosure and editorial policy.
Which kind of cooling company do you need?
Start with the part of the heat path you're buying, because few companies make every part. Heat leaves IT equipment by air or by liquid, and both paths end at the same plant: a facility water loop and the chillers, dry coolers or towers that reject heat outdoors. The diagram shows where each equipment category sits.
| Category | What it does | First question to ask | Companies listing it |
|---|---|---|---|
| Room and row air units | CRAHs (chilled water), CRACs (refrigerant), fan walls and in-row units move server exhaust air across coils | Sensible capacity at your return-air temperature and airflow | 10 |
| Chillers and heat rejection | Chillers, dry coolers, evaporative and free-cooling units reject heat from the facility water loop | Capacity and power at your design ambient and water temperature | 10 |
| CDUs | Separate the facility water from the technology cooling loop and pump coolant to racks | Capacity at your facility water temperature and approach | 18 |
| Cold plates / direct-to-chip | Plates on CPUs and GPUs carry heat into the loop; single-phase water/glycol or two-phase fluid | Which server platforms are supported, and by whom | 9 |
| Rear-door heat exchangers | A water coil on the back of the rack takes heat out of the exhaust air before it reaches the room | kW removed per rack at your water temperature and server airflow | 6 |
| Immersion | Servers sit in, or are sealed with, dielectric fluid that carries heat to a heat exchanger | Fluid type, server compatibility and kW per tank or chassis | 5 |
What each company's own site lists
This table is the directory in one view: 26 companies, the group they're filed under, and the equipment types we found on their own sites. Click a name to jump to its entry and links.
| Company | Group | Air units | Chillers and heat rejection | CDUs | Cold plates / DTC | Rear doors | Immersion | Source |
|---|---|---|---|---|---|---|---|---|
| AAON (BASX) | Air and plant | Yes | – | – | – | – | – | 4 |
| Airedale by Modine | Air and plant | Yes | Yes | Yes | – | – | – | 56 |
| Carrier | Air and plant | – | Yes | Yes | – | – | – | 8 |
| Daikin Applied | Air and plant | – | Yes | Yes | – | – | – | 910 |
| Johnson Controls (Silent-Aire, YORK) | Air and plant | Yes | Yes | Yes | – | – | – | 111213 |
| Mitsubishi Electric (CritiCool) | Air and plant | Yes | Yes | – | – | – | – | 14 |
| Munters | Air and plant | Yes | Yes | Yes | – | – | – | 15 |
| Nortek Data Center Cooling | Air and plant | Yes | – | Yes | – | – | – | 1617 |
| Schneider Electric (Uniflair) | Air and plant | Yes | Yes | Yes | Yes | Yes | – | 1819 |
| STULZ | Air and plant | Yes | – | Yes | – | – | – | 20 |
| Trane | Air and plant | Yes | Yes | Yes | – | – | – | 21 |
| Vertiv | Air and plant | Yes | Yes | Yes | Yes | Yes | Yes | 232425 |
| Accelsius | Direct-to-chip and CDUs | – | – | – | Yes | – | – | 27 |
| Boyd Thermal (Eaton) | Direct-to-chip and CDUs | – | – | Yes | Yes | – | – | 29 |
| Chilldyne | Direct-to-chip and CDUs | – | – | Yes | Yes | – | – | 3110 |
| CoolIT Systems | Direct-to-chip and CDUs | – | – | Yes | Yes | – | – | 32 |
| JetCool (Flex) | Direct-to-chip and CDUs | – | – | Yes | Yes | – | – | 3435 |
| LiquidStack (Trane Technologies) | Direct-to-chip and CDUs | – | – | Yes | – | – | Yes | 3622 |
| nVent | Direct-to-chip and CDUs | – | – | Yes | – | Yes | – | 37 |
| ZutaCore | Direct-to-chip and CDUs | – | – | – | Yes | – | – | 38 |
| Motivair (Schneider Electric) | Rear doors | – | Yes | Yes | Yes | Yes | – | 3940 |
| Rittal | Rear doors | – | – | Yes | – | Yes | – | 42 |
| USystems (ColdLogik) | Rear doors | – | – | – | – | Yes | – | 43 |
| GRC (Green Revolution Cooling) | Immersion | – | – | – | – | – | Yes | 44 |
| Iceotope | Immersion | – | – | – | – | – | Yes | 45 |
| Submer | Immersion | – | – | – | – | – | Yes | 46 |
“Yes” = the product type appears on the company's own site or its parent's. “–” = we didn't find it there. Air units = CRAH, CRAC, fan wall or in-row. DTC = direct-to-chip.
Shortlist builder
FilterCompanies matched
–
Tick at least one equipment type.
How it works: the builder reads the capability table above and lists every company with a “Yes” in any (or every) column you tick, then assembles the matching questions from the vendor checklist below. Example: ticking cold plates and rear doors with “every selected type” returns Motivair, Schneider Electric and Vertiv. It only knows what we found on company websites, so treat a short list as a starting point, not a complete market.
Air-side and plant equipment makers
These 12 companies list room and row air units, chillers and heat rejection, or both, and most now list CDUs as well. They're the usual starting point for a new hall, a CRAH or chiller replacement, or a hybrid hall that mixes air and liquid.
AAON (BASX)
Air unitsAAON's data center page presents its BASX line: DCF fan coil walls, which it describes as “designed for perimeter gallery thermal management,” computer room air handlers (CRAHs) with chilled water, DX and water/glycol options, and direct evaporative cooling units.4
Airedale by Modine
Air units · Chillers and heat rejection · CDUsAiredale says its data center portfolio “includes data center chillers, CRAHs/CRACs, fan walls, in-row coolers,” backed by its IQity controls software.5 Its CDU range, extended with a skid-based design in October 2025, spans “from 400kW up to 2MW and beyond, at a 4K approach.”6 Parent company Modine's shareholders approved renaming it Modexus Solutions in November 2026.7
Carrier
Chillers and heat rejection · CDUsCarrier's data center page lists AquaEdge and AquaForce air-cooled chillers, AquaEdge water-cooled centrifugal chillers, and Carrier coolant distribution units for direct-to-chip liquid cooling, plus lifecycle service for data center thermal systems.8
Daikin Applied
Chillers and heat rejection · CDUsDaikin Applied lists magnetic-bearing, free-cooling and high-ambient data center chillers, and names Alliance Air Products, DDC Solutions and Chilldyne as acquisitions that broaden its range “from chip to facility.”9 Daikin's November 2025 release describes Chilldyne's CDU technology as a negative-pressure system.10
Johnson Controls (Silent-Aire, YORK)
Air units · Chillers and heat rejection · CDUsIts data center page describes Silent-Aire, “a Johnson Controls company,” as specializing in modular data centers and CRAC and CRAHU systems.11 Silent-Aire CDUs, launched in September 2025, range “from 500kW to over 10MW” for in-row or white-space perimeter placement.12 Johnson Controls also sells YORK data center chillers such as the YVAM magnetic-bearing chiller.13
Mitsubishi Electric (CritiCool)
Air units · Chillers and heat rejectionMitsubishi Electric's US critical-facilities site lists the MECH-iC, “a compact, oil-free centrifugal chiller system engineered for warm-water operation,” the MEWALL thermal wall, and a packaged wall-mounted DX system for containerized IT. The CritiCool line is sold through Mitsubishi Electric Critical Power Solutions.14
Mitsubishi Electric Critical Power Solutions data center cooling page
Munters
Air units · Chillers and heat rejection · CDUsMunters Data Center Technologies lists chillers, CDUs, CRAHs, dry coolers and liquid cooling, and says its portfolio “supports air, liquid and hybrid architectures.” Its case studies include Oasis indirect evaporative cooling.15
Nortek Data Center Cooling
Air units · CDUsNortek names StatePoint, ServerCool and FANWALL as its data center cooling technologies.16 Its site announces a skidded CDU configurable from 1 MW to more than 5 MW, and describes the company as part of Madison Air.17
Schneider Electric (Uniflair)
Air units · Chillers and heat rejection · CDUs · Cold plates / DTC · Rear doorsUnder its Uniflair range, Schneider lists air-cooled, free-cooling and water-cooled chillers, perimeter room cooling, and chilled-water and DX in-row units.18 Its US liquid cooling page lists CDUs, direct-to-chip systems and rear door heat exchangers, and its links for those products lead to the site of Motivair, which Schneider controls (see Motivair below).19
STULZ
Air units · CDUsSTULZ USA lists CyberAir chilled-water and DX units, the CyberWall air handler, CyberRow in-row units and the CyberCool CDU USA, and describes its range as computer room air conditioners, air handlers and humidity control for data centers.20
Trane
Air units · Chillers and heat rejection · CDUsTrane's data center pages list data center chillers, air handlers, controls and liquid cooling systems, and describe its chillers, CDUs and controls working as one system.21 Its parent, Trane Technologies, completed its acquisition of LiquidStack in March 2026 (listed below).22
Vertiv
Air units · Chillers and heat rejection · CDUs · Cold plates / DTC · Rear doors · ImmersionVertiv's thermal catalog covers rack, room and in-row cooling, heat rejection, outdoor packaged systems, evaporative free cooling and free-cooling chillers.23 Its CoolChip CDUs run from 70 kW to 2,300 kW in in-rack, in-row and perimeter designs,24 and Vertiv says its “thermal chain” includes direct-to-chip cooling, immersion cooling and rear-door heat exchangers.25 In December 2023 Vertiv agreed to acquire CoolTera, a UK maker of CDUs, secondary fluid networks and manifolds.26
Direct-to-chip liquid cooling: cold plates and CDUs
These 8 companies center on liquid delivered to the chip: cold plates, CDUs, or two-phase systems. Cold plates often arrive inside the server; CoolIT, for example, says server platforms from major OEMs are equipped with its cold plates.32 Ask your server vendor which plates and CDUs are qualified for your platform before you shortlist.
Accelsius
Cold plates / DTCAccelsius makes NeuCool, a two-phase direct-to-chip cooling system; its site says it cools “4500W+ per socket.”27 Johnson Controls announced a strategic investment in October 2025,13 then led Accelsius's $65 million Series B, which closed in January 2026 with Legrand also investing.28
Boyd Thermal (Eaton)
CDUs · Cold plates / DTCEaton completed its acquisition of Boyd Thermal on March 12, 2026.30 Eaton's pages now list CDUs in liquid-to-liquid and liquid-to-air versions, leak-tested liquid cooling loops that combine cold plates, tubing and quick disconnects, and liquid cold plates.29
Chilldyne
CDUs · Cold plates / DTCChilldyne sells direct-to-chip liquid cooling built on what it calls “patented, negative pressure technology,” which it markets as leak-free.31 Daikin Applied announced its acquisition of Chilldyne on November 5, 2025.10
CoolIT Systems
CDUs · Cold plates / DTCCoolIT lists a “full product line of liquid-to-liquid and liquid-to-air CDUs” and says server platforms from major OEMs are equipped with its cold plates.32 Ecolab completed its acquisition of CoolIT on July 2, 2026.33
JetCool (Flex)
CDUs · Cold plates / DTCJetCool says it engineers “microchannel, microconvective, hybrid, embedded silicon” and other heat-transfer designs matched to each chip.34 Flex announced it had acquired JetCool on November 14, 2024; that release also describes a JetCool CDU for racks up to 300 kW.35
LiquidStack (Trane Technologies)
CDUs · ImmersionLiquidStack lists three CDU families: CDU 1.X, CDU 2.X and a GigaModular CDU that it says scales to multi-megawatt capacity and supports 45 °C return water.36 Trane Technologies completed its acquisition of LiquidStack on March 3, 2026; Trane's release describes LiquidStack's direct-to-chip and immersion cooling.22
nVent
CDUs · Rear doorsnVent lists CDUs, a liquid-to-air sidecar unit that supports up to two racks of liquid-cooled IT without a facility water system, and rear door heat exchangers, including an RDHX PRO it rates for racks up to 78 kW.37
ZutaCore
Cold plates / DTCZutaCore's HyperCool is a two-phase direct-to-chip system that removes heat at the processor “through a sealed, closed-loop system” and uses no water.38
Rear-door heat exchanger makers
These 3 companies make rear-door heat exchangers as a core product. nVent, Schneider Electric and Vertiv, listed above, also list rear doors.371925 Rear doors work with air-cooled servers, which makes them an option when a room can't take more heat but the servers aren't built for liquid.
Motivair (Schneider Electric)
Chillers and heat rejection · CDUs · Cold plates / DTC · Rear doorsMotivair lists the ChilledDoor active rear door heat exchanger, which it rates for up to 75 kW per rack, CDUs from a 4U in-rack unit up to 2.5 MW per unit, a liquid-to-air heat dissipation unit (HDU), Dynamic Cold Plates with their manifolds and quick connects, and free-cooling and air-cooled chillers.39 Its September 2025 portfolio release describes the same CDU, ChilledDoor and Dynamic Cold Plate lines.40 Schneider Electric completed the purchase of a 75% controlling stake on February 28, 2025.41
Rittal
CDUs · Rear doorsRittal's US direct liquid cooling page lists a 70 kW rear door heat exchanger with a coolant circulation unit, a 150 kW in-rack CDU and a 1 MW in-row CDU.42
USystems (ColdLogik)
Rear doorsUSystems makes ColdLogik rear door heat exchangers: the CL20 and CL23 active doors, the latter described at 200 kW per rack, and the CL21 passive door.43
Immersion cooling makers
These 3 companies make immersion systems, where dielectric fluid touches the electronics. Vertiv also lists immersion, and Trane's release describes LiquidStack's immersion cooling.2522
GRC (Green Revolution Cooling)
ImmersionGRC presents itself as a single-phase immersion cooling company and sells server immersion cooling systems for data centers, AI, HPC and edge sites.44
Iceotope
ImmersionIceotope's “precision liquid cooling” seals a small amount of dielectric coolant inside each server chassis and passes the heat to a technology cooling system loop through a liquid-to-liquid heat exchanger. It says the design supports inlet coolant above 55 °C.45
Submer
ImmersionSubmer lists the SmartPod EVO immersion system, which it rates at 140 kW+ of heat dissipation, the SmartPod EXO for higher densities, and the MicroPod edge unit with up to 7 kW.46
This list isn't complete. Mechanical contractors, manufacturers' representatives and regional integrators also install and service this equipment, and the right installer may be local to you. Companies can ask to be added or corrected by emailing requests@datacenterserviceproviders.com; see our editorial policy.
Recent acquisitions that change who you're buying from
Several liquid cooling specialists now belong to large HVAC, electrical or water companies, which can change pricing channels, service networks and warranty terms. These are the changes we confirmed from primary announcements; ask any vendor in this table who will support the equipment and honor the warranty.
| Company | Now part of | What was announced | Source |
|---|---|---|---|
| JetCool | Flex | Acquisition announced as done, November 14, 2024 | 35 |
| Motivair | Schneider Electric | Purchase of an initial 75% controlling interest completed February 28, 2025; Schneider expects to buy the remaining 25% in 2028 | 41 |
| Chilldyne | Daikin Applied | Acquisition announced November 5, 2025; Daikin Applied also lists Alliance Air Products and DDC Solutions among its acquisitions | 109 |
| LiquidStack | Trane Technologies | Acquisition completed March 3, 2026 (announced February 10, 2026) | 22 |
| Boyd Thermal | Eaton | Acquisition completed March 12, 2026 | 30 |
| CoolIT Systems | Ecolab | Acquisition completed July 2, 2026 | 33 |
| CoolTera (UK CDU maker) | Vertiv (agreement; we didn't confirm the closing) | Definitive agreement to acquire announced December 4, 2023 | 26 |
| Accelsius | Not acquired; founded by Innventure, with Johnson Controls and Legrand as investors | Johnson Controls’ “multi-million dollar strategic investment” announced October 6, 2025; $65 million Series B led by Johnson Controls, with Legrand, closed January 12, 2026 | 1328 |
| Airedale's parent, Modine | Renamed Modexus Solutions | Shareholders approved the name change, announced November 16, 2026 | 7 |
“Now part of” reflects the announcements cited. Motivair is 75% owned until the planned 2028 purchase of the rest. We didn't verify how each brand is sold or serviced after the deal.
What to ask a cooling vendor before you shortlist
Ask every vendor to state capacity at your conditions, in writing, before you compare prices. A capacity number means little without the temperatures it was rated at. Vertiv, for example, rates its CoolChip CDUs at a stated approach temperature difference, such as 600 kW at 4 °C ATD,24 and Airedale quotes its CDU range “at a 4K approach.”6 The same unit delivers different capacity at a different approach or water temperature.
Flow matters as much as kW. Using NIST's properties for water at 30 °C (995.65 kg/m³ and 4.1798 kJ/kg·K),3 moving 600 kW with a 10 K rise across the loop takes about 865 L/min (229 gpm). At a 5 K rise it takes twice that, about 1,730 L/min. Flow is heat ÷ (density × specific heat × temperature rise), so check that each quote's pumps and pipe sizes match the temperature rise it assumes. Glycol mixtures need more flow; our coolant flow and CDU sizing calculator handles water and PG25 (25% propylene glycol).
| Item | Ask each vendor | Why it matters |
|---|---|---|
| Capacity at stated conditions | Capacity at your facility water supply temperature, loop temperature rise and approach (for CDUs), or return-air temperature and airflow (for air units); ask for the selection printout | Ratings are published at specific conditions, such as 4 °C ATD for Vertiv's larger CDUs.24 Quotes rated at different conditions aren't comparable. |
| Water temperature class | Which ASHRAE liquid cooling class (W17, W27, W32, W40, W45 or W+) the equipment is designed for, and capacity at your warmest expected supply | ASHRAE's classes set facility water supply temperatures from 17 °C (W17) to above 45 °C (W+); from W32 up, ASHRAE lists cooling towers as the primary facility, with chillers only as a supplemental option at W32 and W40.1 |
| Efficiency data source | Where every efficiency or savings figure comes from: test standard, lab, conditions, baseline and date. For computer room air conditioners, whether the model is in the AHRI Directory | AHRI certifies computer and data processing room air conditioners to AHRI Standard 1360 and/or ASHRAE 127 within its capacity scope and requires published ratings to match the AHRI Directory.2 Marketing figures, such as ZutaCore's “up to 82%” energy reduction or GRC's “up to 95% less cooling power,” need a stated baseline.3844 |
| Fluid and water quality | Required coolant and filtration, who supplies and tests it, and what fluid problems void the warranty | Coolant chemistry is an ongoing program, not a one-time fill. Our guide to cooling water treatment programs covers the facility side. |
| Redundancy and controls | Redundancy offered (N+1, N+2), what fails over automatically, and how the unit reports to your building management system (BMS) or data center infrastructure management (DCIM) software | Some CDU lines advertise redundancy options; LiquidStack, for example, lists N+1/N+2 for its GigaModular CDU.36 |
| Service footprint | Who services the equipment in your metro (factory, dealer or contractor), where spares are stocked, and response times written into the contract | Some makers service their own equipment; Munters says it designs, builds and services its systems.15 We didn't verify any company's service coverage. |
| Price breakdown | An itemized quote: equipment, controls, freight, startup, commissioning support, spares and any service contract priced separately, with what is excluded | Bundled prices hide scope differences. We don't publish prices because we didn't verify any company's pricing. |
| Lead time | Written lead time, what starts the clock (purchase order or approved submittals), and whether a factory slot is reserved | Lead times change with demand. We didn't verify lead times for any company on this page. |
| Warranty terms | When coverage starts (shipment or startup), length, parts vs labor, and how leaks or IT damage are handled | Leak-related claims vary by vendor; Chilldyne, for example, markets its negative-pressure system as leak-free.31 Get the actual warranty language, not the marketing line. |
| Testing and commissioning | Factory witness testing, startup support, and participation in integrated systems testing | Liquid systems add pumps, controls and failure modes to test. See commissioning levels and integrated systems testing (IST). |
| Ownership and support | After an acquisition, who sells, services and warrants the product line | Six listed companies changed hands between November 2024 and July 2026 (see the ownership table above). |
What to send cooling companies for comparable quotes
Send every company the same package so the quotes differ by approach, not by guesses about your site.
- Site location and whether it's a new build, an expansion or a retrofit of a live hall.
- IT load in kW or MW, rack count and kW per rack, and how much of the heat goes to liquid vs air.
- Server or GPU platform, if liquid cooling is involved, and any cold plates or CDUs the server maker requires.
- Facility water supply temperature (or ASHRAE W class), available flow, and whether glycol is used.
- Climate data or design ambient temperatures, and any water-use or refrigerant limits.
- Redundancy target (N, N+1, 2N) and the controls or building management system (BMS) the equipment must talk to.
- Space, floor loading and access limits, plus schedule and required delivery date.
- Scope: equipment only, or equipment plus installation, startup, commissioning and a service contract.
Using our form? Put the kW, equipment type and location in the request, along with whatever else from this list you have. You can contact companies from the directory directly, or send one request through the form on this page.
Limits of this directory
This is a snapshot from November 27, 2026. Products, ownership and brand names change; check each company's site before you rely on it. Descriptions and figures such as kW ratings are the companies' own claims, which we haven't tested, and inclusion isn't an endorsement. A dash in the capability table means we didn't find that product on the company's site, not that it isn't offered. We didn't verify US offices, service coverage, lead times, warranty terms, certifications or pricing for any company. This page is for buying equipment; it isn't investment research and says nothing about any company's stock. Nothing here is engineering advice; have a qualified mechanical engineer size and specify the system.
Get cooling quotes through Data Center Service Providers
Send one request with your location, load and the equipment you need. We review it and, where we can identify suppliers or installers that serve your area and list that equipment, share it with up to three of them. They aren't necessarily companies in the directory above. We don't have agreements with any provider yet, so we can't promise how many will respond or how quickly. Any provider that does contacts you directly, and you decide whether to hire anyone. It's free for buyers. Providers who receive requests may pay us a referral fee in future; the referral disclosure explains how. We're a referral service, not a manufacturer, contractor or engineering firm, and routing a request isn't an endorsement. Read how it works, or go to the request form.
Sources
- ASHRAE TC 9.9 Reference Card: 2021 Equipment Thermal Guidelines for Data Processing Environments (5th edition), ASHRAE. Liquid cooling classes W17 to W+ and their facility water supply temperatures. Checked 2026-11-27.
- Datacom Cooling certification program, AHRI (Air-Conditioning, Heating, and Refrigeration Institute). Program scope (AHRI Standard 1360 / ASHRAE 127) and the rule that published ratings must match the AHRI Directory. Checked 2026-11-27.
- Isobaric properties for water at 1 bar, 20 to 50 °C, NIST Chemistry WebBook (Standard Reference Database 69). At 30 °C: density 995.65 kg/m³, specific heat 4.1798 kJ/(kg·K). Used for the worked flow example. Checked 2026-11-27.
- Data Centers, AAON. Checked 2026-11-27.
- Edge Data Center Cooling, Airedale by Modine. Checked 2026-11-27.
- Airedale by Modine unveils skid-based CDU for scalable data center efficiency, Airedale by Modine, October 30, 2025. Checked 2026-11-27.
- Shareholders approve corporate name change to Modexus Solutions, Modine, November 16, 2026. Checked 2026-11-27.
- Data Center Thermal Management, Carrier Commercial. Checked 2026-11-27.
- Data Center Cooling Solutions, Daikin Applied. Checked 2026-11-27.
- Daikin Applied expands data center offering with acquisition of Chilldyne, Daikin Industries, November 5, 2025. Checked 2026-11-27.
- Data Centers, Johnson Controls. Checked 2026-11-27.
- Johnson Controls expands thermal management offering with scalable liquid cooling solution, Johnson Controls, September 8, 2025. Checked 2026-11-27.
- Johnson Controls announces investment in data center liquid cooling company Accelsius, Johnson Controls, October 6, 2025. Also names the YORK YVAM magnetic-bearing chiller. Checked 2026-11-27.
- Data Center Cooling Solutions, Mitsubishi Electric (Critical Power Solutions). Checked 2026-11-27.
- Munters Data Center Technologies, Munters. Checked 2026-11-27.
- RackBank specifies Nortek’s StatePoint cooling technology, Nortek Data Center Cooling, July 15, 2021. Names StatePoint, ServerCool and FANWALL as Nortek technologies. Checked 2026-11-27.
- Nortek announces 5MW CDU for liquid cooling, Nortek Data Center Cooling (repost of DatacenterDynamics), August 28, 2026. Checked 2026-11-27.
- Uniflair Master Range, Schneider Electric. Checked 2026-11-27.
- Liquid cooling solutions for AI and high-density data centers, Schneider Electric United States. Checked 2026-11-27.
- Data Center Cooling & Humidity Control Products, STULZ USA. Checked 2026-11-27.
- Data Center Cooling Solutions, Trane Commercial HVAC. Checked 2026-11-27.
- Trane Technologies completes acquisition of LiquidStack, Trane Technologies, March 3, 2026. Checked 2026-11-27.
- Thermal Management product catalog, Vertiv. Checked 2026-11-27.
- Vertiv CoolChip CDU, 70 to 2300 kW, Vertiv. Model table states each capacity at an approach temperature difference (ATD). Checked 2026-11-27.
- Vertiv expands liquid cooling portfolio in EMEA to accelerate AI-ready data centre deployments, Vertiv, May 26, 2026. Checked 2026-11-27.
- Vertiv acquisition of CoolTera Ltd. boosts liquid cooling portfolio, Vertiv, December 4, 2023. Announces a definitive agreement to acquire CoolTera. Checked 2026-11-27.
- Accelsius home page (NeuCool), Accelsius. Checked 2026-11-27.
- Accelsius closes $65 million Series B funding led by Johnson Controls; Legrand joining round, Innventure (founder of Accelsius), January 12, 2026. Checked 2026-11-27.
- Cloud data center cooling, Eaton (Boyd Thermal). Checked 2026-11-27.
- Eaton completes acquisition of leading liquid-cooling solutions provider Boyd Thermal, Eaton, March 12, 2026. Checked 2026-11-27.
- Chilldyne home page, Chilldyne. Checked 2026-11-27.
- Data Center Products, CoolIT Systems. Checked 2026-11-27.
- Ecolab has closed its acquisition of CoolIT Systems, CoolIT Systems, July 2, 2026. Checked 2026-11-27.
- Direct-to-Chip Liquid Cooling Technology, JetCool. Checked 2026-11-27.
- Flex acquires JetCool to expand data center and power portfolio, JetCool, November 14, 2024. Checked 2026-11-27.
- LiquidStack home page (CDU families), LiquidStack. Checked 2026-11-27.
- Data Center Liquid Cooling Solutions, nVent. Checked 2026-11-27.
- ZutaCore home page (HyperCool), ZutaCore. Checked 2026-11-27.
- AI & HPC Liquid Cooling Systems (products), Motivair by Schneider Electric. Checked 2026-11-27.
- Schneider Electric unveils liquid cooling portfolio with Motivair, Motivair by Schneider Electric, September 29, 2025. Checked 2026-11-27.
- Schneider Electric completes transaction to acquire Motivair Corporation, Schneider Electric, February 28, 2025. Checked 2026-11-27.
- Direct Liquid Cooling in Hyperscale Data Centers, Rittal (US). Checked 2026-11-27.
- Rear Door Heat Exchangers (ColdLogik), USystems. Checked 2026-11-27.
- GRC home page, GRC (Green Revolution Cooling). Checked 2026-11-27.
- How precision liquid cooling technology works, Iceotope. Checked 2026-11-27.
- Immersion cooling for computer components, Submer. Checked 2026-11-27.