Cooling · High-density and AI racks

Data center liquid cooling: choose the approach, size the CDU, get integrator quotes

Liquid cooling is no longer optional for current rack-scale AI systems: NVIDIA lists 120 kW of designed rack power for GB200 NVL72 and 135 kW for GB300 NVL72, and their compute trays are cooled through cold plates.12 Rear-door heat exchangers suit air-cooled servers in existing rooms, single-phase direct-to-chip with a coolant distribution unit (CDU) is the usual path for GPU racks, and immersion fits sites that control their own server choice. Your IT maker's coolant, flow and water-quality requirements decide the design, so use the comparison and calculator below to scope it, then send one request and we'll look for up to three independent integrators that fit. We're a directory and referral service; we don't design or install cooling.

Updated · How we research

When does a rack need liquid cooling?

A rack needs liquid cooling when its IT maker ships it that way, and for current NVIDIA rack-scale AI systems that is already the case. NVIDIA's DGX guide says the compute trays are cooled by liquid that runs through rack manifolds and then through cold plates on the CPUs and GPUs, while networking and storage devices stay air-cooled.2 For other hardware, the trigger is a rack heat load your room can't remove with air, or a customer contract that specifies liquid-ready capacity.

The gap between AI racks and the typical room is large. Uptime Institute's 2025 survey puts the average of operators' typical (modal) rack densities at almost 9 kW, and more than 80% of operators say their facility has no racks above 30 kW.6 The rack figures below are published by NVIDIA and its hardware and infrastructure partners. They describe different boundaries, so compare like with like.

Published rack power for NVIDIA NVL72 racks versus typical data center racks. kW per rack. Sources as cited; checked November 27, 2026.
System or benchmarkPublished figureWhat the figure meansSource
GB200 NVL72 (NVIDIA)120 kWDesigned rack power, 1.2 kW per GPU; the DGX guide gives rack consumption of about 120 kWNVIDIA12
GB200 NVL72 by HPE132 kW TDP; about 192 kW EDPpThermal design power, nominal; peak electrical design power is 1.5 × TDP, and HPE suggests sizing busway for 192 kWHPE3
Supermicro GB200 NVL72132 kW total; 125 to 135 kW operatingDatasheet's total power for the rack's power shelves, and its operating power rangeSupermicro4
GB300 NVL72 (NVIDIA)135 kWDesigned rack power, 1.4 kW per GPUNVIDIA1
Vertiv GB300 NVL72 reference architectureUp to 142 kWRack density the cooling and power design supportsVertiv (June 2025)5
Typical operator (Uptime 2025)Almost 9 kWAverage of operators' modal rack densities, global surveyUptime Institute6

Use the IT maker's figure for the cooling load and the larger electrical figure for power distribution. The two are not the same number.

Is liquid cooling better than air? For heat-dense chips it moves more heat with less air handling, but it isn't a drop-in swap: it adds a second fluid loop, water-quality control and new failure modes. ASHRAE TC 9.9 notes that, in earlier research with medium-power processors, the time between a CDU pump failure and processor throttling was as little as 23 seconds.10 If your racks are air-cooled and well within your room's capacity, liquid cooling adds cost without solving a problem.

Which liquid cooling approach fits your racks?

Pick the approach from the hardware first, then the building. If the server is built for cold plates, you need direct-to-chip cooling and a CDU. If the servers are air-cooled and the room is the bottleneck, a rear-door heat exchanger is the least invasive option. Immersion is a different way of building the white space and suits sites that choose their own servers.

Rear-door heat exchangers: passive and active

A rear-door heat exchanger (RDHx) replaces the rack's rear door with a water coil, so server exhaust air is cooled before it reaches the room. A passive door has no fans and relies on the servers' own fans to push air through the coil; an active door adds its own variable-speed fans.14 The servers stay air-cooled, so nothing changes inside them.

Capacity depends on the door, water temperature and flow. Motivair's ChilledDoor is an active door: its own fans pull room air through the servers.17 HPE, which sells the doors, lists them at 5 to 17 kW per rack for the smallest model and 55 to 75 kW for the largest.16 In a DOE case study published in 2010, passive doors at Lawrence Berkeley National Laboratory running 9 gpm each at 72 °F supply water removed about 48% of 66 kW of server heat, with the rest left to the room.15 The coil must stay above the room's dew point: HPE's specification has the doors running on facility water 2 °C (4 °F) above the maximum anticipated dew point, and requires a CDU to create a warmer secondary loop when the water is at or below the dew point.16 Door makers are grouped in our rear-door heat exchanger directory.

Direct-to-chip cold plates: single-phase and two-phase

Direct-to-chip (DTC or DLC) cooling bolts cold plates onto the hottest chips and pumps coolant through them. In single-phase systems the coolant stays liquid; Schneider Electric describes it as usually 75% water and 25% glycol in a closed loop.12 The heat goes to a CDU, where a heat exchanger passes it to facility water or, with a liquid-to-air CDU, to the room's existing cooling units.13 Other parts of the server, such as network cards, drives and power supplies, still need air.2

In two-phase cold plates the fluid boils on the chip. Vertiv describes a low-pressure dielectric liquid boiling in evaporators; Schneider says the fluid is often a dielectric or refrigerant.1312 ZutaCore, a two-phase vendor, condenses the vapor in a CDU and lists in-rack CDUs from 20 kW to 120 kW.18 Schneider's view is that two-phase has a higher heat transfer rate at the cold plate but costs more up front and complicates fluid management, and that operators mostly choose single-phase because it is simpler and quicker to deploy.12 That's a vendor's opinion; ask any two-phase bidder which IT platforms have qualified their cold plates. Cold plate and CDU makers are listed in our directory of direct-to-chip suppliers.

Immersion cooling: single-phase and two-phase

Immersion cooling submerges the servers in a dielectric fluid inside a tank. In single-phase immersion the fluid stays liquid and is pumped through a heat exchanger. GRC lists its ICEraQ tanks from 13 kW with 32 °C water up to 368 kW with 13 °C water, and some models keep 8U of dry space for air-cooled equipment and PDUs.19 Single-phase fluids include hydrocarbon oils and synthetic esters. In a 2026 study of immersion fluids, the polyalphaolefin, paraffinic, mineral oil and synthetic ester samples had specific heats of about 1.8 to 2.1 kJ/kg·K at 25 °C, roughly half that of PG25 at 3.88 to 3.89 kJ/kg·K.2023

In two-phase immersion the fluid boils on the components and the vapor condenses on a coil above the bath. GIGABYTE's LiquidStack solution page describes a fluid boiling at 50 °C and recommends 3M Fluorinert fluids.21 3M says it completed its exit from PFAS manufacturing at the end of 2025, so confirm the long-term supply and regulatory status of any fluorinated fluid before you commit.22 For tank and fluid vendors, see the immersion cooling makers in our directory.

Comparison of liquid cooling approaches

Liquid cooling approaches compared. Density examples are published product or case-study figures, not limits; other columns are our editorial summary of the cited sources. Checked November 27, 2026.
ApproachWhere the heat goesPublished density examplesFacility waterRetrofit fitFluidsUpkeep to plan for
Passive rear doorRack exhaust air into a water coil; server fans move the airLBNL case: about 48% of 66 kW of server heat removed (DOE, 2010)15Chilled or treated water above dew point, or a CDU loop16Good: servers unchanged; needs water piped to each doorWater or water-glycolCoil cleanliness, water quality, condensation checks
Active rear doorSame, with door fansMotivair ChilledDoor: 5 to 17 kW up to 55 to 75 kW per rack, by model1716As above16Good; adds fan power and controlsWater or water-glycolAs above, plus door fans
Single-phase direct-to-chipChip heat into coolant; the rest of the server to air2NVIDIA NVL72: 120 to 135 kW designed rack power1Liquid-to-liquid CDU on facility water, or liquid-to-air CDU134Needs liquid-ready servers, CDU, secondary piping and leak detectionPG25 common; treated water11Coolant sampling, filters, CDU pumps, quick disconnects
Two-phase direct-to-chipChip heat boils a dielectric or refrigerant12ZutaCore in-rack CDU: 20 to 120 kW18Depends on the condenser; ask the vendorNeeds servers qualified for the vendor's cold plates and fluid loopDielectric fluid or refrigerant1312Fluid charge and leak checks; vendor-specific
Single-phase immersionAll submerged components into a dielectric fluidGRC: 13 kW at 32 °C water to 368 kW at 13 °C water19Water to the tank's heat exchanger; capacity falls as water warms19Hard: tanks replace racks; heavy; servers must be approved for immersionHydrocarbon oils, synthetic esters20Fluid testing, server handling out of the bath
Two-phase immersionComponents boil the fluid; vapor condenses on a coil21No published figure foundWater to the condenser coilHard; sealed tanks and vapor managementFluorinated fluids; check supply22Vapor loss control, fluid make-up

"Retrofit fit" and "upkeep" are our summary, not a standard. Confirm every number against the product data for the exact model and water temperature you will run.

How a liquid cooling loop works: FWS, CDU and TCS

A direct-to-chip system has two water loops joined by a CDU. The facility water system (FWS) carries heat to the cooling towers, dry coolers or chillers. The technology cooling system (TCS) is a separate, cleaner loop that runs from the CDU to the rack manifolds and cold plates. ASHRAE TC 9.9's first design recommendation for cold plate deployments is to use a CDU so the two loops stay separate, because they have different requirements, fluid quality above all.10

Liquid cooling loop: heat rejection, facility water system, CDU, technology cooling system and rack From top to bottom: a heat rejection plant (cooling tower, dry cooler or chiller) connects through the facility water system to a coolant distribution unit. The CDU holds a heat exchanger, pumps and filters and connects through a separate technology cooling system loop to the rack manifolds, which feed cold plates on the GPUs and CPUs in each server tray. Heat from fans, network cards, drives and power supplies still goes to room air. Heat rejection Cooling tower, dry cooler or chiller CDU (coolant distribution unit) Heat exchanger, pumps, filters, controls and expansion tank Liquid-cooled rack FWS: facility water Supply set by ASHRAE W-class (W17 to W+) TCS: secondary loop PG25 or treated water, supply per S-class (S30–S50) Tray: cold plates on GPUs Tray: cold plates on CPUs Manifolds and hoses Still air-cooled (room air): fans, NICs, drives, power shelves Down arrows = supply · Up arrows = return
Typical single-phase direct-to-chip loop. The CDU keeps facility water (FWS) and the technology cooling system (TCS) separate, which ASHRAE TC 9.9 recommends.10 A liquid-to-air CDU replaces the top two blocks and sends the heat to room air instead.13 A rear-door heat exchanger sits on facility water or on a CDU loop, depending on dew point.16 Drawing by Data Center Service Providers.

CDU types: in-rack, in-row and liquid-to-air

CDUs come in three forms, and the choice depends on how many racks one unit serves and whether you have facility water.

  • In-rack CDU. Sits inside the rack it serves. Supermicro offers a 4U, 250 kW in-rack CDU for GB200 NVL72, with redundant power supplies and dual hot-swap pumps.4
  • In-row CDU. A floor-standing unit that serves several racks. HPE rates its in-row CDU for GB200 NVL72 at 1.3 MW and says one CDU supports at most 8 racks.3 The calculator's defaults use that rating and rack count.
  • Liquid-to-air CDU. Rejects the TCS heat into the room through a coil and fans, so it needs no facility water. Supermicro lists 180 kW and 240 kW options for facilities without cooling tower and water supply.4 Vertiv notes these use the existing room cooling units for heat rejection.13 The room must then remove the full rack load.

ASHRAE liquid cooling classes: W-classes and S-classes

ASHRAE uses two sets of classes. W-classes set the facility water supply temperature, and S-classes set the maximum TCS coolant supply temperature to the IT equipment. The W-classes were renamed in the 2021 fifth edition of the Thermal Guidelines so the name carries the upper limit: W17 (formerly W1), W27 (W2), W32 (W3), W40 (new), W45 (W4) and W+ (W5).8

ASHRAE facility water (FWS) liquid cooling classes, 2021 Thermal Guidelines, Table 3.1. Minimum water temperature for all classes is 2 °C (35.6 °F).
ClassFacility water supply, maxPrimary facilitiesSupplemental facilities
W1717 °C (62.6 °F)Chiller/cooling towerWater-side economizer (cooling tower)
W2727 °C (80.6 °F)Chiller/cooling towerWater-side economizer (cooling tower)
W3232 °C (89.6 °F)Cooling towerChiller or district heating system
W4040 °C (104 °F)Cooling towerChiller or district heating system
W4545 °C (113 °F)Cooling towerDistrict heating system
W+Above 45 °C (113 °F)Cooling towerDistrict heating system

Source: ASHRAE TC 9.9 reference card for the 2021 Thermal Guidelines.7 ASHRAE describes W17/W27 sites as typically chiller-cooled with an optional economizer, W32/W40 as typically operated without chillers in most locations, and W45/W+ as typically operated without chillers.7

The S-classes are newer. ASHRAE TC 9.9 introduced them for TCS supply temperature in its Datacom Encyclopedia, a subscription product.9 The table below is as published in the December 2024 ASHRAE Journal summary of the TC 9.9 resiliency bulletin; TC 9.9 said it expected to revise the S-classes as chip power rises.10

ASHRAE TCS (secondary loop) liquid cooling classes as published December 2024. Minimum temperature for all classes is 2 °C (3.6 °F) above the measured room air dew point.
ClassMax TCS supplyTypical FWS heat rejection
S3030 °C (86 °F)Chiller/cooling tower
S3535 °C (95 °F)Chiller/cooling tower
S4040 °C (104 °F)Cooling tower
S4545 °C (113 °F)Cooling tower/dry cooler
S5050 °C (122 °F)Dry cooler

Source: ASHRAE Journal, December 2024, Table 2.10 Check the current Datacom Encyclopedia before you write a specification.

How to use them: take the S-class from the IT maker's thermal requirements, then work back through the CDU to the warmest facility water that still meets it. TC 9.9 recommends lower S-classes only in high-density zones, because warmer water lets the cooling plant run more efficiently and economize for more hours.10 In 2021 ASHRAE wrote that most cold plate solutions could run easily on W32 water.8

How to size coolant flow and CDUs

Size the CDU from the heat that goes into the liquid, the temperature rise the IT maker allows, and the facility water temperature you can deliver. The flow follows from basic heat balance: heat equals mass flow × specific heat × temperature rise. The DOE's rear-door case study uses the US form of the same rule: BTU/h = 500 × gpm × ΔT (°F) for water.15

Coolant flow and CDU calculator

Calculator

Flow per rack

198.1 L/min

Flow per rack (US)

52.3 gpm

Flow per kW

1.50 L/min per kW

All racks

1,056 kW · 1,585 L/min · 419 gpm

CDUs

1 to carry the load (N) · 2 with one spare (N+1)

Heat split

132 kW to liquid · 0 kW left for room air, per rack

Basis: 1.0278 kg/L, 3.89 kJ/kg·K, ΔT 10 K

Flow (L/s) = liquid heat (kW) ÷ [density (kg/L) × specific heat (kJ/kg·K) × ΔT (K)]; × 60 for L/min; ÷ 3.785 for US gpm. Liquid heat = rack power × the share captured by liquid. Water properties are NIST values at 1 atm; PG25 values are Dow's typical properties for DOWFROST LC 25, both at the mean fluid temperature you pick. CDU count = total liquid heat ÷ CDU rating, rounded up, plus one for N+1. CDU ratings depend on the water temperatures and flow they were rated at, so use the figure for your conditions. Planning aid only: the IT maker's flow and pressure requirements govern, and an engineer must design the system.

Worked example. One 132 kW rack with all of its heat taken by PG25 at a 10 K (18 °F) rise and a 30 °C mean temperature: 132 ÷ (1.0278 kg/L × 3.89 kJ/kg·K × 10 K) = 3.30 L/s, or 198 L/min (52.3 gpm). With water instead, the flow is 190 L/min (50.3 gpm).2324 The US rule gives the same water answer: 132 kW is about 450,400 BTU/h, and 450,400 ÷ (500 × 18) ≈ 50 gpm.15 PG25 at a 10 K rise works out to 1.50 L/min per kW, which matches the 1.5 L/min per kW that Schneider calls the industry flow standard.12 Eight such racks put 1,056 kW into the liquid, about 1,585 L/min (419 gpm), so one CDU rated at HPE's 1.3 MW covers the load and a second gives N+1, if the CDU holds that rating at your water temperatures.3

Use the calculator to scope. The real numbers come from the IT maker. ASHRAE TC 9.9 says to obtain and follow the liquid-cooled equipment maker's requirements for TCS temperature, flow rate, pressure drop, maximum operating pressure, fluid quality and wetted materials.10

Six checks before you pick a CDU size

  1. Heat capture ratio. Ask the IT maker what share of rack heat goes to liquid at your conditions. ASHRAE notes liquid-cooled equipment can still put a significant load on the room's air cooling.10 Enter that share in the calculator to see the residual air load.
  2. Rating conditions. CDU capacity changes with water temperature. GRC, for example, rates one immersion CDU at 45 kW with 32 °C water and 90 kW with 13 °C chilled water.19 Ask every bidder for capacity at your facility water supply temperature, flow and TCS setpoint.
  3. Active redundancy. Run the spare pumps or CDUs, don't leave them idle. TC 9.9 reports TCS temperature jumps of as much as 27 °C (48.6 °F) when CDU pumps changed over without active redundancy.10
  4. Ride-through. TC 9.9 recommends UPS power for the FWS and TCS pumps, thermal storage for the chiller plant and buffer tanks on the return, plus transient modeling.10
  5. Pressure. Model the full pressure cascade, including flush and fill pressures, static height, relief valve and expansion tank settings, and set relief valves below the IT equipment's rated maximum working pressure.11
  6. Filtration. Cold plate channels can be 50 microns or smaller, so TCS filtration and monitoring follow the IT maker's specification, not FWS practice.10

Which coolant: water, PG25 or dielectric fluid?

Most single-phase direct-to-chip loops run a propylene glycol and water mix. ASHRAE TC 9.9's May 2026 bulletin says a nominal 25% by volume propylene glycol mix (PG25) is commonly used as the single-phase TCS design condition.11 Dow's PG25 product for direct-to-chip cooling is freeze-protected to −10 °C (14 °F) and has a specific heat of 3.94 kJ/kg·K at 50 °C, against about 4.18 for water.2324 That's why PG25 needs about 4% more flow than water for the same heat and temperature rise in the calculator.

Stick to the coolant the system was designed for. The bulletin warns that changing concentration alters viscosity, pressure drop, pump operating point and heat exchanger performance, and it recommends lab testing the concentration and quality at first fill, after any significant make-up and on the maker's schedule.11 Dielectric fluids are the exception, used in two-phase cold plates and in immersion tanks, as covered above.

Water quality is tighter on the TCS than on facility water. TC 9.9's typical guidelines, as published in ASHRAE Journal:10

Typical water quality guidelines for facility water (FWS) and technology cooling system (TCS) loops, ASHRAE TC 9.9 via ASHRAE Journal, December 2024. Confirm against the IT maker's specification. The table gives no particulate removal guidance.
ParameterFWSTCS
pH7 to 98.0 to 9.5
Corrosion inhibitor(s)RequiredRequired
BiocideNot listedRequired
Sulfide<10 ppm<1 ppm
Sulfate<100 ppm<10 ppm
Chloride<50 ppm<5 ppm
Bacteria<1,000 CFU/mL<100 CFU/mL
Total hardness (as CaCO₃)<200 ppm<20 ppm
ConductivityNot listed0.2 to 20 micromho/cm
Total suspended solidsNot listed<3 ppm
Residue after evaporation<500 ppm<50 ppm
Turbidity<20 NTU<20 NTU

Inhibited glycol products have their own limits: Dow lists electrical conductivity above 2,000 micromho/cm for its PG25, so follow the IT maker's approved-fluid list rather than the water table for a glycol loop.23

TC 9.9 says the facility should have water treatment expertise on staff or work with a qualified fluid treatment provider.10 For the facility water side, see our guide to cooling water treatment programs, which also covers closed-loop and TCS water quality.

Retrofit or new build: what changes in the room

A retrofit has to fit liquid into a room designed for air; a new build can plan the water, power and structure around it. The table lists what to check in each case.

Retrofit versus new build checks for liquid cooling. Editorial checklist drawing on the cited sources.
ItemRetrofit (existing hall)New build
Heat rejectionIs there spare chilled or condenser water at the right temperature? If not, liquid-to-air CDUs or rear doors move the load back to the room13Pick the W-class first; warmer water allows fewer chiller hours7
PipingRoute secondary piping overhead or under floor; HPE supports both top-feed and bottom-feed secondary loops3Plan stainless or approved materials and passivation from the start; TC 9.9 warns that field welding after passivation can release metal into the coolant11
Floor loadingAn HPE GB200 NVL72 rack weighs about 3,245 lb fully loaded on a 1,068 × 600 mm footprint, roughly 470 lb/ft² over that footprint (our arithmetic). Compare with your floor's structural rating3Design slabs for liquid-filled racks, CDUs and, for immersion, filled tanks
PowerCheck that busway and breakers can carry peak draw; HPE suggests provisioning for 192 kW EDPp per GB200 NVL72 rack3Put CDU and FWS pumps on UPS, as TC 9.9 recommends10
Leak detectionAdd sensing at CDUs, manifolds and under racks, tied to the BMS and DCIM; the NVIDIA DGX GB rack includes its own leak detection2Same, plus drainage and containment designed in
Air managementKeep containment for the air-cooled share of the loadSize air handling for the residual load from the heat capture ratio10
CommissioningFlush, clean and test new branches before connecting live equipment; protect existing loops from contaminationHydraulic and thermal commissioning with load banks or thermal test vehicles10

Commissioning the liquid loop

Commissioning is where many liquid cooling problems are caught, or created. TC 9.9 recommends hydraulic and thermal commissioning with thermal test vehicles or the actual IT equipment, and notes that system behavior can change once the final IT gear is installed.10 Its 2026 bulletin adds that flush water should meet TC 9.9's TCS water quality guidelines or ASTM D1193 Type II, that cleanliness should be verified by fluid testing before sensitive equipment is connected, and that degassing works best at elevated temperatures, often reached only during commissioning with load banks or in normal operation.11 For how CDU functional tests fit into the wider data center commissioning process, including integrated systems testing with load banks, see our commissioning guide.

What does data center liquid cooling cost?

We haven't found a credible, current published benchmark for installed liquid cooling cost, so this page gives no dollar figures. Quotes vary with the approach, the number of racks, the facility water work and how much of the room must change. Ask bidders to price these lines separately:

  • CDUs, including redundancy, and their rating at your water temperatures;
  • secondary piping, manifolds, hoses and quick disconnects;
  • facility water work: taps, valves, heat exchangers, pumps, controls;
  • leak detection and monitoring integration;
  • coolant, initial fill, flushing, cleaning and passivation;
  • commissioning, including load banks or thermal test vehicles;
  • electrical work for CDUs and any added busway capacity;
  • structural assessment if racks or tanks are heavier than the floor was designed for;
  • a maintenance plan: coolant sampling, filter changes and CDU service.

Ongoing work belongs in your maintenance program: TC 9.9 calls for monitoring coolant quality and filtration as the IT maker directs.10 Our maintenance guide covers CDU service alongside chiller and CRAH maintenance.

Liquid cooling project checklist

  1. Get the IT maker's thermal requirements. Rack power, heat capture ratio, coolant, S-class, flow, pressure drop, maximum pressure, water quality and wetted materials.10
  2. Choose the approach. Cold plates if the hardware requires them; rear doors for air-cooled racks; immersion only with server makers' support.
  3. Confirm heat rejection. Facility water temperature (W-class) and spare capacity, or a liquid-to-air CDU plan.
  4. Size flow and CDUs. Use the calculator, then get CDU capacity at your conditions, with N+1 running.
  5. Check the room. Floor loading, piping routes, power for peak draw, leak detection and residual air load.
  6. Specify fluid quality. Design-basis coolant, filtration, sampling plan and who owns water treatment.
  7. Plan commissioning. Flushing, passivation records, fill and venting, hydraulic and thermal tests with load banks or thermal test vehicles.1110
  8. Request quotes. Send the same scope to each bidder and compare line by line.

Limits of this guide

This guide summarizes published manufacturer documents, ASHRAE TC 9.9 publications and one DOE case study, checked November 27, 2026. The S-class table is as published in ASHRAE Journal in December 2024; ASHRAE's Datacom Encyclopedia, which we couldn't review, may have revised it. Product capacities apply to the stated models and water temperatures only. The calculator uses typical fluid properties and ignores pressure drop, pump sizing and heat exchanger approach. The comparison table's retrofit and upkeep columns are our judgment. Nothing here replaces the IT maker's requirements or a design by a licensed engineer. We don't recommend or rank any manufacturer or integrator.

What to send integrators for an accurate quote

Integrators can price a liquid cooling project quickly if you send the hardware, the building constraints and the schedule:

  • number of racks and kW per rack, and the server or GPU platform (for example GB200 or GB300 NVL72);
  • the IT maker's coolant, flow, S-class and water quality requirements, if you have them;
  • approach under consideration: rear door, direct-to-chip or immersion;
  • facility water available: temperature, spare capacity and distance to the white space, or none;
  • retrofit or new build, raised floor or slab, and overhead or under-floor piping preference;
  • redundancy target for CDUs and pumps;
  • site location, access rules and target ready-for-service date.

Need a vendor list first? Browse our directory of cooling manufacturers and integrators. Hosting GPU racks rather than building? Start with colocation services and check each facility's supported density and cooling limits before you compare prices.

Request liquid cooling quotes

Send one request with your racks, platform and facility details. A person reviews it and looks for up to three independent integrators or manufacturers that serve your market and do this kind of work. If we can't find a fit, we'll tell you. They contact you directly, and you decide whether to hire anyone. It's free for buyers. Providers may pay us a referral fee; see the referral disclosure. Data Center Service Providers is a directory and referral service, not a contractor or engineer, and we don't design, install or supervise cooling work. Here's how requests are handled.

Request liquid cooling quotes

Sources

  1. NVIDIA Mission Control Software Administration Guide 2.3.1: FAQ (power reservation examples for GB200/GB300 NVL72), NVIDIA, Page last updated October 12, 2026. Table of per-GPU maximum power and designed rack power: GB200 1.2 kW and 120 kW; GB300 1.4 kW and 135 kW. Checked 2026-11-27.
  2. NVIDIA DGX GB Rack Scale Systems User Guide, NVIDIA. Sections 1.2 (compute trays), 1.4 (power shelves: rack power consumption approximately 120 kW) and 1.7 (leak detection). Checked 2026-11-27.
  3. NVIDIA GB200 NVL72 by HPE QuickSpecs, Hewlett Packard Enterprise. Rack TDP, EDPp, busway guidance, dimensions, weight, CDU description and in-row CDU rating. Checked 2026-11-27.
  4. Supermicro NVIDIA GB200 NVL72 datasheet, Supermicro. Power shelves (8 × 1U 33 kW, total power 132 kW), operating power 125 to 135 kW, liquid cooling options. Checked 2026-11-27.
  5. Vertiv develops energy-efficient cooling and power reference architecture for the NVIDIA GB300 NVL72 platform, Vertiv (press release), June 11, 2025. Checked 2026-11-27.
  6. Uptime Institute Global Data Center Survey 2025, Uptime Institute, 2025. Rack density benchmarks (n=710 and n=709 operators). Checked 2026-11-27.
  7. ASHRAE TC 9.9 Reference Card: 2021 Equipment Thermal Guidelines for Data Processing Environments (Table 3.1, liquid cooling), ASHRAE, 2021 (Thermal Guidelines, fifth edition). Checked 2026-11-27.
  8. Emergence and Expansion of Liquid Cooling in Mainstream Data Centers (white paper), ASHRAE TC 9.9, 2021. Checked 2026-11-27.
  9. ASHRAE Technical Committee 9.9 home page (Datacom Encyclopedia announcement), ASHRAE TC 9.9. States that the Datacom Encyclopedia introduced S classes for TCS supply temperature and expanded TCS and FWS fluid quality guidance. Checked 2026-11-27.
  10. New TC 9.9 Technical Bulletin: Liquid Cooling: Resiliency Guidance for Cold Plate Deployments (ASHRAE Journal Data Centers column), ASHRAE Journal; T. Davidson, D. Quirk, J. Seter, D. Demetriou (hosted by DLB Associates), December 2024. Summarizes the 2024 TC 9.9 bulletin: S-class table, design and operation recommendations, FWS and TCS water quality table. Checked 2026-11-27.
  11. ASHRAE TC 9.9 Technical Bulletin: TCS Coolant Integrity and System Readiness Best Practices, ASHRAE TC 9.9, Issued May 2026. Checked 2026-11-27.
  12. Two-phase vs single-phase direct-to-chip liquid cooling: Which is right for AI data centers in 2026, Schneider Electric blog (Greg Alexander, Motivair by Schneider Electric), May 5, 2026. Checked 2026-11-27.
  13. Understanding direct-to-chip cooling in HPC infrastructure: A deep dive into liquid cooling, Vertiv, March 18, 2025. Checked 2026-11-27.
  14. How rear door heat exchangers (RDHx) support high-density rack cooling, Vertiv, September 8, 2025. Checked 2026-11-27.
  15. Data Center Rack Cooling with Rear-door Heat Exchanger (case study), U.S. Department of Energy FEMP / Lawrence Berkeley National Laboratory, June 2010. Passive RDHx at LBNL (underlying Taylor Engineering case study covers 2007 to 2009); flow range, heat calculation and share of heat removed. Checked 2026-11-27.
  16. Motivair Liquid Cooled Doors QuickSpecs, Hewlett Packard Enterprise, Version 9, September 21, 2026. Door model capacities (M8 5–17 kW to M16 55–75 kW), dew point and water pressure requirements. Checked 2026-11-27.
  17. ChilledDoor rear door heat exchanger, Motivair (Motivair by Schneider Electric). Describes the ChilledDoor as an active rear door heat exchanger that uses fans to pull room air through the servers. Checked 2026-11-27.
  18. HyperCool solutions, ZutaCore. Checked 2026-11-27.
  19. ICEraQ: Immersion Cooling Tank for Data Centers, GRC (Green Revolution Cooling), Page modified November 17, 2026. Checked 2026-11-27.
  20. Comparative evaluation of dielectric liquids for single-phase immersion cooling of electronics, International Journal of Heat and Mass Transfer, vol. 265 (Aflatounian et al.), September 1, 2026. Table of tested fluids with density and specific heat. Checked 2026-11-27.
  21. Two-Phase Immersion Cooling with LiquidStack, GIGABYTE. Checked 2026-11-27.
  22. PFAS uses and applications: our PFAS exit, 3M. Checked 2026-11-27.
  23. DOWFROST LC Heat Transfer Fluid technical data sheet (PG25 and PG55), Dow (copy hosted by distributor Glycol Sales). Density and specific heat of DOWFROST LC 25 by temperature; typical properties, not specifications. Checked 2026-11-27.
  24. Isobaric properties for water at 0.101325 MPa, 20 to 50 °C, NIST Chemistry WebBook, SRD 69. Checked 2026-11-27.